Home > Products > Filtration > GORE® Cooling Filters > Applications Performance and Construction Materials
Applications Performance and Construction Materials
Application Performance
|
Temperature Range:
|
-40°C to +65°C
|
|
Humidity:
|
0 to 100% RH
|
|
Typical Initial dP:
|
50 - 100 Pa
|
|
Typical Final dP:
|
200 - 250 Pa
|
|
Typical Filter Lifetime:
|
3 -5 Years
|
|
Filter Efficiency:
|
99% (@ 0.3 μm and larger particles, 1 cm/sec)
|
Construction Materials
|
Frame:
|
Anodized Aluminum
|
|
Filter Media:
|
Microporous Expanded
Polytetrafluoroethylene (ePTFE)
Membrane with Non-Woven support
|
|
Potting:
|
Polyurethane
|
|
Gaskets (optional):
|
Closed Cell Polyurethane
|
|
Backplate (optional):
|
Anodized Aluminum
|
|
|