Application Performance

Temperature Range:

-40°C to +65°C

Humidity:

0 to 100% RH

Typical Initial dP:

50 - 100 Pa

Typical Final dP:

200 - 250 Pa

Typical Filter Lifetime:           

3 -5 Years

Filter Efficiency:

99% (@ 0.3 μm and larger particles, 1 cm/sec)

Construction Materials

Frame:

Anodized Aluminum

Filter Media:

Microporous Expanded
Polytetrafluoroethylene (ePTFE)
Membrane with Non-Woven support

Potting:

Polyurethane

Gaskets (optional):

Closed Cell Polyurethane

Backplate (optional):

Anodized Aluminum


 

 